Ammonia compressor VKh-350 — Rogan Brewery JSC

← Full catalogue

INDUSTRIAL CASE STUDY|FOOD INDUSTRY|AMMONIA COMPRESSORS · POWER CONSUMPTION

TEST PROTOCOL · ROGAN BREWERY JSC

Ammonia compressor VKh-350: same cooling output at lower power draw

Rogan Brewery JSC, compressor station  ·  approved by chief engineer E. A. Gavrilenko; signed by the head of the electrical shop and the head of the planning department

Kharkiv, Ukraine  ·  testing 10–25 August 1998

PRODUCTXADO RVSin the protocol — “treatment by RVS technology”
TEST OBJECTAmmonia compressor VKh-350inv. No. 13 — treated · inv. No. 15 — control, untreated
DOCUMENT TYPETest protocol,
approved by the chief engineer

Key results

12.7%
drive power draw, untreated 156.0 → treated 136.2 kW
10.2%
average hourly consumption, before treatment 140.2 → after 125.9 kW
UNITCONDITION AT START OF TESTINGWHAT WAS MEASURED
Compressor VKh-350, inv. No. 13Treated with XADO RVS; 200 kW electric drive, cos φ = 0.9Metered consumption before and after treatment; drive current and power
Compressor VKh-350, inv. No. 15Control, untreated; same shop, same modelDrive current and power at the same hours, at the same valve setting

Electricity metering: the same compressor before and after treatment

PERIODMETERING DURATIONAVERAGE HOURLY CONSUMPTION
Before treatment, 10–11 August23 h140.2 kW
After treatment, 12–13 August24 h125.9 kW
Change10.2 % lower

Three-phase meter via a 400/5 A current transformer; readings were taken every 2 hours at the same setting of the capacity valve.

Comparison with an untreated compressor of the same model, 17–25 August

PARAMETERINV. No. 15 — UNTREATEDINV. No. 13 — TREATED
Average current across three phases245–275 A220–240 A
Drive power draw145.8–163.6 kW130.6–142.5 kW
Mean power over 18 readings156.0 kW136.2 kW

Measurements taken with clamp meters at a fully open valve on both units. The plant's planning department estimated the saving at 427 kWh per day.

Protocol conclusion

The commission of Rogan Brewery JSC recorded two conclusions obtained by different methods. From three-phase metering on the treated unit itself: “as a result of applying RVS technology, the saving in electricity consumption by compressor VKh-350 inv. No. 13 amounts to 10.2 %”. Compared with the neighbouring compressor of the same model, running in the same shop and in the same duty mode without treatment: “as a result of treating compressor VKh-350 inv. No. 13 by RVS technology, electricity consumption decreased by 12.7 %”. The output for the test period was fixed by an order of the shop manager — the unit consumed less energy while producing the same amount of cold. The plant's planning department estimated the saving at 427 kWh per day and 12,830 kWh per month on a single compressor.

The results apply to VKh-350 ammonia compressors with a 200 kW electric drive under the conditions of a food plant compressor station; on other equipment and in other duty modes the figures may differ. RVS is an obsolete XADO designation, the zero-generation compounds; the current product generation is revitalizants. The original protocol with signatures and stamp is published in full and available for download.

Current equivalent