SCREW COMPRESSOR TREATMENT REPORT, 2019
Bell Air AED 22A compressor: electricity savings without disassembly or repair
signed and stamped by both parties
Key result
| EQUIPMENT | CONDITION AT START OF TESTING | WHAT WAS MEASURED |
|---|---|---|
| Bell Air AED 22A screw air compressor, 22 kW drive | In service since 2013: elevated oil temperature, noise and vibration, longer air charging time due to worn parts | Current on all three phases of the drive motor and working pressure — under load and at idle |
Current of the 22 kW drive electric motor
| MODE AND PHASE | BEFORE TREATMENT | AFTER 50 H OF OPERATION | CHANGE |
|---|---|---|---|
| Under load, phase I | 43.9 A | 34.5 A | −21.4 % |
| Under load, phase II | 40.84 A | 34.7 A | −15.0 % |
| Under load, phase III | 41.3 A | 34.5 A | −16.5 % |
| Idle, phase I | 19.8 A | 18.2 A | −8.1 % |
| Idle, phase II | 20.3 A | 18.6 A | −8.4 % |
| Idle, phase III | 20.9 A | 17.7 A | −15.3 % |
The current drop was recorded on all three phases in both modes; the results section of the report states an average reduction in power consumption of 21.4 %.
Working pressure in the system
| MODE | BEFORE TREATMENT | AFTER 50 H OF OPERATION | RATED |
|---|---|---|---|
| Idle | 4.9 bar | 6.3 bar | 7 bar |
| Under load | 6.9 bar | 6.9 bar | 7 bar |
Under load the compressor held pressure close to the rated 0.7 MPa even before treatment — there was no room to rise; the gain of 1.4 bar came in the idle mode.
Report conclusion
The results refer to the Bell Air AED 22A screw air compressor with a 22 kW drive and were obtained after 50 h of operation following treatment; on other units and under different operating conditions the figures may differ. The treatment was performed and the report prepared by PT XADO Indonesia. The original report, signed and stamped by both parties, is published in full and available for download.