INDUSTRIAL CASE STUDY|POWER GENERATION|DIESEL GENSET · CYLINDER-PISTON GROUP

EQUIPMENT TREATMENT REPORT · SABSON ENERGY, ADEN

MTU 4000 G63 V16: cylinders back to nominal, power close to rated

Cylinders reached nominal pressure, the spread across cylinders narrowed, the oil ran cooler. 1–2.5 bar — peak cylinder pressure, 27–29 → 28.5–30 bar (nominal 30); 5 % — diesel power output, 1535 → 1612 kW (nominal 1635); 14 % — oil temperature, 121 → 104 °C (2020).

Sabson Energy Ltd, diesel power plant  ·  treatment and supervision performed by a XADO Chemical Group engineer; report signed by the customer's technical management

Aden, Yemen  ·  treatment 19–23.04.2020 · monitoring up to 561 h of operation

PRODUCTXADO Gel-Revitalizant®
for Diesel Engine
5 stages of 520 ml · oil system flush XADO VitaFlush
TEST OBJECTMTU 4000 G63 V16 diesel gensetV16, 76.3 l, 16 cylinders · rated power 1635 kW (ISO 3046)
DOCUMENT TYPEEquipment treatment
report
Four signatures of the parties, seal of Sabson Energy FZE

Key results

1–2.5bar
peak cylinder pressure,27–29 → 28.5–30 bar (nominal 30)
5%
diesel power output,1535 → 1612 kW (nominal 1635)
14%
oil temperature,121 → 104 °C
UNITCONDITION AT THE START OF TESTSWHAT WAS MEASURED
MTU 4000 G63 V16 diesel<br/>16 cylinders, 76.3 l, 2011Generator power loss, spread of pressure across the cylinders, increased oil consumption; endoscopy of the cylinder-piston group — multiple scratches on the cylinder wallsCylinder pressure, diesel power output, oil temperature and oil consumption

Peak cylinder pressure, bar — before treatment and after 561 h of operation

CYLINDERBEFORE TREATMENTAFTER 561 H
12728.5
22728.5
327.530
427.530
527.530
62728.5
72830
828.530
92830
102930
112930
122729
132830
1427.529
152930
162830

The nominal 30 bar was reached in 11 of the 16 cylinders, the spread narrowed from 27–29 to 28.5–30 bar. Measured with a compression gauge at 1500 rpm, coolant temperature 55 °C.

Power, oil temperature and oil consumption over operating hours

PARAMETERBEFORE TREATMENTAFTER 100 HAFTER 561 H
Diesel power output, kW153515411612
Oil temperature, °C121119104
Oil consumption, l/h32.72.5

Measurements taken at 1500 rpm. Between 100 and 561 h four more check measurements were made: power was rising, oil temperature was falling monotonically. Engine rating — 1635 kW (ISO 3046).

Report conclusions

Before treatment, endoscopy of the cylinder-piston group showed multiple scratches on the cylinder walls, none of the 16 cylinders delivered the nominal pressure, and the generator was losing power. Following the treatment and 561 h of monitoring, the parties recorded: 1. The scheduled cylinder liner replacement interval changed from ≈20 000 to more than 25 000 h of operation: cavitation wear was reduced, which extended the liner service life by 25 %. 2. Oil consumption fell from 3.1 to 2.5 l/h, which is 19.4 %. 3. Output power rose from 1535 to 1612 kW, which is 5 %. 4. Visually, the scratches on the cylinder walls healed over or decreased in size. 5. The amount of wear debris in the oil decreased according to oil analysis data.

Current equivalent

How such units are treated: Internal combustion engineCylinder-piston group

About this result: CompressionTemperature

Limits of this report: The results refer to an MTU 4000 G63 V16 diesel genset at 1500 rpm under continuous power plant operation; on other equipment and in other duty modes the figures may differ.

Request a pilot for this unit

XADO Pilot Testing Programme

Application submitted by

Pilot treatment on the enterprise's equipment

  • any oil- or grease-lubricated assemblies: gearboxes, engines, compressors, bearings and others;
  • treatment within the regular operating cycle, without halting production;
  • instrumental measurements before and after: vibration, temperature, power consumption or current;
  • procedure for the specific assembly, dose calculation and support from a XADO engineer.

After the application, a XADO engineer will agree the units and the list of measurements with you.